Home / Building automation / ekey KNX connect
Developed by netyard · Fingerprint meets KNX
ekey KNX connect.
Our EKEY KNX CONNECT module integrates ekey access systems of the home, MULTI and NET series into your KNX installation – based on the ISE Smart Connect KNX Programmable, communicating via IP.
€829.00 incl. 19% VAT, plus shipping
What you need
Requirements
- EKEY KNX CONNECTMounted and connected to power, the KNX bus and your network.
- ekey RS-485 LAN converterekey net CVLAN RS-485 module (order no. 100340) or ekey home CV LAN RS-485 module (order no. 100460).
- ETS 4 or laterFor parameterisation on the KNX side.
- Static IP addressFor the module – please assign it statically instead of via DHCP.
Compatibility
The LAN converter sends a UDP packet whenever something happens on the RS-485 bus – our module evaluates it and triggers the matching KNX events.
ekey.NET
Software version 4.4.4 or later. CVLAN NET devices need at least firmware 3.2.58.18.
Protocol type: rare v2
ekey home (MULTI)
With the latest firmware installed.
Protocol type: multi
Converter settings
- Enable UDP transmission
- Receiver IP = address of the EKEY KNX CONNECT
- Separator: underscore (_)
- Receiver port of your choice, ideally above 49151 – identical in the KNX parameters
Commissioning
Ready in four steps.
- InstallConnect the module to power, the KNX bus and your network.
- Import the product fileImport it into ETS – or search the ETS online catalogue for “ise smart connect KNX Programmable”.
- Load the data point listLoad the matching list (NET or MULTI) onto the device via the “Plug-in” context menu.
- ConfigureSet the protocol type (MULTI or NET) and the UDP port, and assign a static IP address.
Technical details
Communication objects
The update trigger is normally 0 and switches to 1 for one second after every update. Detailed protocol descriptions can be found in the ekey manuals.
ekey NET – 14 objects
Including event code, terminal ID, fingerprint scanner serial number, relay ID, user ID, finger ID (including PIN code and RFID), event name, date, time, user name and update trigger.
ekey MULTI – 13 objects
Including user data and status, finger ID, key ID, scanner serial number, action code, digital input, date, time and update trigger.
Gira HomeServer logic modules
Two logic modules (NET and MULTI) evaluate serial number, action code, user ID and finger ID and use the update signal to trigger KNX actions.
ekey manuals
Downloads
All files for the module
File version: 12 April 2022
Contact
Questions about the integration?
As an ekey premium partner and KNX specialist, we help with selection, commissioning and programming. We speak English.
- Phone +49 211 415596-0
- E-mail post@netyard.de
- Address netyard AG, Schanzenstr. 40, 40549 Düsseldorf, Germany